中文摘要:
      电晕噪声不同于的传统的电气设备噪声,其发声位置高、频带宽、声源分散,是750kV变电站噪声控制的薄弱环节。本文以西北某750kV变电站为例,使用紫外成像仪定位了36处主要电晕噪声点,基于噪声实测和全站声场仿真分析,研究了电晕噪声对变电站声环境的影响。针对主要电晕点的实际情况,提出了具体的电晕噪声防治措施。治理措施在该站750kV I母第6间隔电晕噪声治理中获得实际应用,治理后I母线下噪声平均降低1.1dB(A),邻近处厂界噪声平均降低3.3dB(A),取得了较为明显的效果。
英文摘要:
      Corona noise position is high and scattered, and its frequency bandwidth is wide. This makes it different from the noise of traditional electrical equipment. This paper takes a 750kV substation in Northwest China as an example, 36 main corona noise points have been located using an ultraviolet imager. Based on the noise measurement and the sound field simulation analysis of the whole station, the influence of corona noise is studied. Specific measures to prevent and control corona noise are proposed for the main corona points. The treatment measures have been practically applied in the substation. After treatment, the noise under bus I is reduced by 1.1dB(A) on average, and the noise at the nearby plant boundary is reduced by 3.3dB(A) on average.
DOI:10.11684/j.issn.1000-310X.2022.01.006
中文关键词: 变电站  电晕  噪声
英文关键词: Substation  Corona  Noise
基金项目:
作者单位E-mail
吴健 西安交通大学 yobdc54@163.com 
赵亚林* 国网陕西省电力公司电力科学研究院 yobdc54@163.com 
耿明昕 国网陕西省电力公司电力科学研究院  
刘志远 国网宁夏电力有限公司 liuzhiyuann@nx.sgcc.com.cn 
王绿 国网陕西省电力公司电力科学研究院 wanglv@dky.sn.sgcc.com.cn 
薛志伟 国网陕西省电力公司  
王帆 大唐宝鸡第二发电有限责任公司  