文章摘要
沈海平,费彬,蔡宜君,闵捷.凸组合的变电站噪声有源控制算法*[J].,2025,43(3):580-587
凸组合的变电站噪声有源控制算法*
Active noise control algorithm for substation noise with convex combination
投稿时间:2024-01-16  修订日期:2025-04-30
中文摘要:
      为了改进有源噪声控制系统在实际变电站场景运行时的稳定性,特别是针对突发性、大强度冲击性噪声的鲁棒性,设计了滤波-x组合对数最小平均绝对值 (FxCLLMA) 算法。在算法的代价函数中融入了误差绝对值及其对数变换两种凸函数的线性组合,其特点是只需要维持一套滤波器的实时运行,系统开销与滤波-x最小均方(FxLMS)算法接近。实际变电站噪声控制结果表明FxCLLMA算法在稳态噪声时的性能与FxLMS算法接近,而在突发性、大强度冲击性噪声时的鲁棒性优于FxLMS算法。
英文摘要:
      To improve the stability of active noise control systems in practical substation applications, especially the robustness against sudden and high-intensity impulse noise, the filtered x combined logarithm least mean absolute value (FxCLLMA) algorithm was designed. The cost function of the algorithm incorporates a linear combination of two convex functions, i.e., the absolute value of error and its logarithmic transformation. Its characteristic is that it only needs to maintain the real-time operation of one adaptive filter, and the system overhead is similar to that of the filtered x least mean square (FxLMS) algorithm. The simulation verification of actual substation noise shows the effectiveness and robustness of the FxCLLMA algorithm.
DOI:10.11684/j.issn.1000-310X.2025.03.006
中文关键词: 有源噪声控制  FxLMS算法  凸组合  变电站噪声
英文关键词: Active noise control  Filtered-x LMS algorithm  Convex combination  Substation noise  
基金项目:
作者单位E-mail
沈海平 国网江苏省电力有限公司无锡供电分公司 Hpshen@126.com 
费彬* 国网江苏省电力有限公司无锡供电分公司 fbin_zj@163.com 
蔡宜君 国网江苏省电力有限公司无锡供电分公司 916481836@qq.com 
闵捷 国网江苏省电力有限公司无锡供电分公司 591906882@qq.com 
摘要点击次数: 4
全文下载次数: 8
查看全文   查看/发表评论  下载PDF阅读器
关闭